Hosting infrastructure

This case covers servers, storage and internal networking at a site with a known inventory. The assessment can cover the whole site or resources reserved for a service. The Cloud case covers public resources whose physical hardware is unknown.

Prepare the data​

InputUnitBoundary
Inventory and manufactureDevices, kg CO₂eStorage and networking equipment included
Annual IT energykWhBefore site cooling and power losses
PUEDimensionlessSame site and period as IT energy
Resource share reserved for the service%Documented allocation, distinct from CPU load
Direct water consumptionL/kWh ITOptional; unknown unless provided

Total site energy is IT energy × PUE. PUE does not multiply manufacture or user-device energy. A whole-site meter already includes auxiliary energy; applying PUE again would count it twice.

Detailed method from site to service​

Consolidate the physical inventory​

The inventory distinguishes servers, storage, network equipment and site installations. Each group has a quantity, period IT energy and per-device manufacture with lifetime. Redundant and standby equipment belongs to provided capacity even with little activity.

Iservice=a[PUE felectricity∑iqiEiT+∑iqiMiTLi]I_{service}=a\left[PUE\,f_{electricity}\sum_i q_i E_iT+\sum_i q_iM_i\frac{T}{L_i}\right]

aa is a uniform reserved-resource share here. Heterogeneous infrastructure may need separate keys for CPU, RAM, storage and network. Allocations must not exceed total inventory; vacant capacity should remain identifiable.

Available dataCorrect conversion
IT equipment energyMultiplication by compatible site PUE
Total site energyDirect use without another PUE multiplier
Power and duration by stateSum of watts × hours, converted to kWh
Service reservation shareDocumented key, distinct from CPU utilization

Water and other installations​

If WUE means liters consumed per IT kWh, Vwater=EIT×WUEV_{water}=E_{IT}\times WUE. Interpretation depends on whether the source describes consumption or withdrawal and covers a full year or a season. Direct site water does not replace the water footprint of electricity or manufacture.

Colocation, sharing and availability​

In colocation, a meter may cover a rack, room or entire site. Its boundary must match PUE and the relevant service shares. Low CPU load does not imply zero power: memory, fans, storage and power supplies keep operating.

Reservation-time allocation suits dedicated capacity. Shared capacity requires explicit resource keys and idle allocation. Redundancy ensuring availability belongs to the benefiting service.

Building, UPS and cooling manufacture requires separate inventories and lifetimes. PUE covers their effect on operational electricity, not their manufacture; it does not implicitly include those contributions.

Check consistency​

Reconciliation relates IT totals to meters and site totals to billed consumption, with documented boundaries. Differences in periods or units can explain a discrepancy without an efficiency gain. Cloud and virtualization rules describe virtualized hardware.

Complete the boundary​

Manufacture of the building, cooling and backup systems requires a separate inventory. Direct water remains in litres; it cannot be added to a characterized water indicator in equivalent cubic metres. See Datacenter.

The result is framed by boundary and functional unit, allocation and double counting.

Electricity factors come from the D4B 2025 snapshot1. Prefilled activity and hosting values are exercise assumptions. Factors and conventions are available below the simulator.

Changing PUE from 1.8 to 1.2 reduces site energy by one third at constant IT energy. Manufacture stays unchanged. A reduction in CPU load alone does not justify a proportional reduction in energy or allocation.

Interactive example​

This example applies the calculations and limitations described above.

The prefilled scenario contains ten servers and five switches. Energy and manufacturing values are exercise assumptions.

Ex: ten 400 W servers and five 30 W switches consume (10 × 0.4 + 5 × 0.03) × 8,760 = 36,354 kWh IT/year. With PUE 1.8, site consumption is 65,437.2 kWh/year.

The exercise assumes 275 kg CO₂e manufacture per server, 30 kg per switch and a five-year lifetime. Allocated manufacture is 580 kg/year. With the France 2025 factor, the subtotal is 2,669.22 kg CO₂e/year.

Example inputs
Equipment factors
Equipment factors
Adjust assumptions
Calculated subtotal2,669 kg CO₂e
2,669 kg CO₂e / year

Not assessed: Direct water not provided ; Building, cooling and backup: manufacture excluded.

Result and activity breakdown

Contributionkg CO₂e
Allocated manufacture580
Use-phase electricity · 65,440 kWh2,089
  • Equipment energy : 36,350 kWh

Prefilled activity and hosting values are example assumptions. The result covers climate impact; unassessed contributions remain identified.

Simulator factors and conventions

Electricity: D4B 2025 national averages. Use country does not change manufacture. Network factors remain unknown until supplied; they must cover the full path, manufacture and operation included. In this illustration, the distance from the D4B per-GB·km model is incorporated upstream into the per-GB route factor.

Annual energy per device, all power states included. For hosting, enter IT energy before PUE. Prefilled inventory profiles are assumptions from this page’s worked example.

Footnotes​

  1. Digital4Better, D4B 2025 snapshot. Snapshot 77cae4a, 2025 data; reviewed 16 October 2026. ↩